6. Description of Parameters
- 181 -
6
Value
Function
Description
50
Clear running time
this time
When terminal set for this function becomes on, current running time of
the AC drive is cleared. This function must be supported by F8-42 and F8-
53.
51
Two-wire control/
Three-wire control
This function enables the AC drive to switch over between two-wire
control and three-wire control. If F4-11 is set to two-wire control mode 1,
the AC drive switches over to three-wire control mode 1 when terminal set
for this function becomes on.
52
Reverse running
prohibited
When terminal set for this function becomes on, reverse running of the
AC drive is prohibited. It is the same as function of F8-13.
53 to 59
Reserved
-
Function Code
Parameter Name
Setting Range
Default
F4-35
DI1 delay
0.0s to 3600.0s
0.0s
F4-36
DI2 delay
0.0s to 3600.0s
0.0s
F4-37
DI3 delay
0.0s to 3600.0s
0.0s
When state of DI terminals changes, these three function parameters set delay time of the
change. Now the drive supports delay function on DI1, DI2 and DI3 only.
Function Code
Parameter Name
Setting Range
Default
F4-38
DI active mode
selection 1
DI2 active mode:
0: High level active
1: Low level active
DI1 active mode:
0: High level active
1: Low level active
DI3 active mode:
0: High level active
1: Low level active
DI5 active mode:
0: High level active
1: Low level active
DI4 active mode:
0: High level active
1: Low level active
00000
Summary of Contents for MD290 Series
Page 1: ......
Page 79: ...3 Electrical Installation 78 3 ...
Page 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Page 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Page 227: ...7 Interfaces and Communication 226 7 ...
Page 285: ...10 Troubleshooting 284 11 ...
Page 349: ......
Page 350: ......