6. Description of Parameters
- 146 -
6
6.5 Control Performance
6.5.1 V/F Curve
Ƶ
Linear, Multi-point and Square V/F Curve
Function Code
Parameter Name
Setting Range
Default
F3-00
V/F curve setting
0: Linear V/F
1: Multi-point V/F
2: Square V/F
10: V/F separation
6SHFL¿F9)VHSDUDWLRQ
0
F3-01
Torque boost
¿[HGERRVW
0.1% to 30%
Model
dependent
F3-02
Cut-off frequency of torque
boost
0.00 Hz to max. frequency
50.00 Hz
F3-03
Multi-point V/F frequency 1
0.00 Hz to F3-05
0.00 Hz
F3-04
Multi-point V/F voltage 1
0.0% to 100.0%
0.0%
F3-05
Multi-point V/F frequency 2
F3-03 to F3-07
0.00 Hz
F3-06
Multi-point V/F voltage 2
0.0% to 100.0%
0.0%
F3-07
Multi-point V/F frequency 3
F3-05 to rated motor
frequency (F1-04)
0.00 Hz
F3-08
Multi-point V/F voltage 3
0.0% to 100.0%
0.0%
1. General constant-torque linear V/F curve
Figure 6-36 General constant-torque linear V/F curve
Output frequency
Output voltage
F1-02
(Rated voltage)
F1-01
(Rated frequency)
F3-01
(Torque boost)
Output voltage and output frequency change linearly when below rated frequency. It is
applicable to general mechanical drive applications such as conveyors where the load
torque is constant against the speed range.
Summary of Contents for MD290 Series
Page 1: ......
Page 79: ...3 Electrical Installation 78 3 ...
Page 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Page 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Page 227: ...7 Interfaces and Communication 226 7 ...
Page 285: ...10 Troubleshooting 284 11 ...
Page 349: ......
Page 350: ......