- 145 -
Figure 6-2 Acceleration/Deceleration time
Time (t)
Output frequency
(Hz)
Set frequency
Acceleration/Deceleration
base frequency
t1
t2
Set deceleration time
Actual acceleration time
Actual deceleration time
Set acceleration time
The I5300 provides totally four groups of acceleration/deceleration time for selection. You
can perform switchover by using a DI terminal.
•
Group 1: P0-17, P0-18
•
Group 2: P8-03, P8-04
•
Group 3: P8-05, P8-06
•
Group 4: P8-07, P8-08
F
unction Code
Parameter Name
Setting Range
Default
P
0-19
Acceleration/Deceleration time unit
0:1s
1: 0.1s
2: 0.01s
1
To satisfy requirements of different applications, the I5300 provides three acceleration/
deceleration time units, 1s, 0.1s and 0.01s.
Note
Modifying this parameter will make the displayed decimal places change and corresponding
acceleration/deceleration time also change.
F
unction Code
Parameter Name
Setting Range
Default
P
0-21
F
requency offset of auxiliary frequency
source for X and Y operation
0.00 Hz to maximum
frequency (
F
0-10)
0.00 Hz
This parameter is valid only when the frequency source is set to "X and Y operation". The
final frequency is obtained by adding the frequency offset set in this parameter to the X and
Y operation result.
I5300 User Manual Description of Function Codes
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...