Description of Function Codes
I5300 User Manual
- 200 -
Figure 6-25 Diagram of the overcurrent stall protection function
Output
current
Output
frequency
(Hz)
Set
frequency
Overcurrent stall
protective current
Time (t)
Time (t)
Acceleration
process
Deceleration
process
Constant-
speed process
F
unction Code
Parameter Name
Setting Range
Default
P
9-07
Short-circuit to ground upon power-
on
0: Disabled
1: Enabled
1
It is used to determine whether to check the motor is short-circuited to ground at power-on
of the AC drive. If this function is enabled, the AC drive's UVW will have voltage output a
while after power-on.
F
unction Code
Parameter Name
Setting Range
Default
P
9-09
F
ault auto reset times
0–20
0
It is used to set the times of fault auto resets if this function is used. After the value is
exceeded, the AC drive will remain in the fault state.
F
unction Code
Parameter Name
Setting Range
Default
P
9-10
DO action during fault auto reset
0: Not act
1: Act
0
It is used to decide whether the DO acts during the fault auto reset if the fault auto reset
function is selected.
F
unction Code
Parameter Name
Setting Range
Default
P
9-11
Time interval of fault auto reset
0.1s–100.0s
1.0s
It is used to set the waiting time from the alarm of the AC drive to fault auto reset.
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...