Description of Function Codes
I5300 User Manual
- 172 -
These parameters are used to set the valid mode of DI terminals.
•
0: High level valid
The DI terminal is valid when being connected with COM, and invalid when being
disconnected from COM.
•
1: Low level valid
The DI terminal is invalid when being connected with COM, and invalid when being
disconnected from COM.
F
unction Code
Parameter Name
Setting Range
Default
P
4-40
AI2 input signal selection
0: Voltage signal
1: Current signal
0
AI2 supports voltage/current output, which is determined by jumper. After setting the jumper,
perform corresponding setting in P4-40.
Group
P
5: Output Terminals
The I5300 provides an analog output (AO) terminal, a digital output (DO) terminal, a relay
terminal and a FM terminal (used for high-speed pulse output or open-collector switch signal
output) as standard. If these output terminals cannot satisfy requirements, use an optional
I/O extension card that provides an AO terminal (AO2), a relay terminal (relay 2) and a DO
terminal (DO2).
F
unction Code
Parameter Name
Setting Range
Default
P
5-00
F
M terminal output mode
0: Pulse output (
F
MP)
1: Switch signal output (
F
MR)
0
The FM terminal is programmable multiplexing terminal. It can be used for high-speed pulse
output (FMP), with maximum frequency of 50 kHz. Refer to P5-06 for relevant functions of
FMP. It can also be used as open collector switch signal output (FMR).
F
unction Code
Parameter Name
Default
P
5-01
F
MR function (open-collector output terminal)
0
P
5-02
Relay function (T/A-T/
B
-T/C)
2
P
5-03
Extension card relay function (P/A-P/
B
-P/C)
0
P
5-04
DO1 function selection (open-collector output terminal)
1
P
5-05
Extension card DO2 function
4
These five parameters are used to select the functions of the five digital output terminals.
T/A-T/B-T/C and P/A-P/B-P/C are respectively the relays on the control board and the
extension card.
The functions of the output terminals are described in the following table.
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...