I5300 User Manual Function Code Table
- 91 -
F
unction
Code
Parameter Name
Setting Range
Default
Property
P
4-33 AI curve selection
Unit's digit (AI1 curve selection)
321
☆
Curve 1 (2 points, see P4-13 to
P4-16)
Curve 2 (2 points, see P4-18 to
P4-21)
Curve 3 (2 points, see P4-23 to
P4-26)
Curve 4 (4 points, see A6-00 to
A6-07)
Curve 5 (4 points, see A6-08 to
A6-15)
Ten's digit (AI2 curve selection)
Curve 1 to curve 5 (same as AI1)
Hundred's digit (AI3 curve
selection)
Curve 1 to curve 5 (same as AI1)
P
4-34 Setting for AI less than
minimum input
Unit's digit (Setting for AI1 less
than minimum input)
000
☆
0: Minimum value
1: 0.0%
Ten's digit (Setting for AI2 less
than minimum input)
0, 1 (same as AI1)
Hundred's digit (Setting for AI3
less than minimum input)
0, 1 (same as AI1)
P
4-35 DI1 delay time
0.0–3600.0s
0.0s
★
P
4-36 DI2 delay time
0.0–3600.0s
0.0s
★
P
4-37 DI3 delay time
0.0–3600.0s
0.0s
★
P
4-38 DI valid mode selection 1
Unit's digit (DI1 valid mode)
00000
★
0: High level valid
1: Low level valid
Ten's digit (DI2 valid mode)
0, 1 (same as DI1)
Hundred's digit (DI3 valid mode)
0, 1 (same as DI1)
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...