- 189 -
F
unction Code
Parameter Name
Setting Range
Default
P
8-12
F
orward/Reverse rotation dead-zone time
0.0–3000.0s
0.0s
It is used to set the time when the output is 0 Hz at transition of the AC drive forward rotation
and reverse rotation, as shown in the following figure.
Figure 6-16 Forward/Reverse rotation dead-zone time
Output
frequency
(Hz)
Forward
rotation
Reverse
rotation
Dead-zone
time
F
unction Code
Parameter Name
Setting Range
Default
P
8-13
Reverse control
0: Enabled
1: Disabled
0
It is used to set whether the AC drive allows reverse rotation. In the applications where
reverse rotation is prohibited, set this parameter to 1.
F
unction Code
Parameter Name
Setting Range
Default
P
8-14
Running mode when set
frequency lower than
frequency lower limit
0: Run at frequency lower limit
1: Stop
2: Run at zero speed
0
It is used to set the AC drive running mode when the set frequency is lower than the
frequency lower limit. The I5300 provides three running modes to satisfy requirements of
various applications.
F
unction Code
Parameter Name
Setting Range
Default
P
8-15
Droop control
0.00–10.00 Hz
0.00 Hz
This function is used for balancing the workload allocation when multiple motors are used
to drive the same load. The output frequency of the AC drives decreases as the load
increases. You can reduce the workload of the motor under load by decreasing the output
frequency for this motor, implementing workload balancing between multiple motors.
F
unction Code
Parameter Name
Setting Range
Default
P
8-16
Accumulative power-on time threshold
0–65000 h
0 h
I5300 User Manual Description of Function Codes
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...