- 175 -
F
unction Code
Parameter Name
Default
P
5-06
F
MP function selection
0
P
5-07
AO1 function selection
0
P
5-08
AO2 function selection
1
The output pulse frequency of the FMP terminal ranges from 0.01 kHz to "Maximum FMP
output frequency" (P5-09). The value of P5-09 is between 0.01 kHz and 100.00 kHz.
The output range of AO1 and AO2 is 0–10 V or 0–20 mA. The relationship between pulse
and analog output ranges and corresponding functions is listed in the following table.
Table 6-6 Relationship between pulse and analog output ranges and corresponding
functions
Value
F
unction
Range (Corresponding to Pulse or Analog
Output Range 0.0%–100.0%)
0
Running frequency
0 to maximum output frequency
1
Set frequency
0 to maximum output frequency
2
Output current
0 to 2 times of rated motor current
3
Output torque (absolute value)
0 to 2 times of rated motor torque
4
Output power
0 to 2 times of rated power
5
Output voltage
0 to 1.2 times of rated AC drive voltage
6
Pulse input
0.01–100.00 kHz
7
AI1
0–10 V
8
AI2
0–10 V (or 0–20 mA)
9
AI3
0–0 V
10
Length
0 to maximum set length
11
Count value
0 to maximum count value
12
Communication setting
0.0%–100.0%
13
Motor rotational speed
0 to rotational speed corresponding to
maximum output frequency
14
Output current
0.0–1000.0 A
15
Output voltage
0.0–000.0 V
16
Output torque (actual value)
-2 times of rated motor torque to 2 times of
rated motor torque
F
unction Code
Parameter Name
Setting Range
Default
P
5-09
Maximum
F
MP output frequency
0.01–100.00 kHz
50.00 kHz
If the FM terminal is used for pulse output, this parameter is used to set the maximum
frequency of pulse output.
I5300 User Manual Description of Function Codes
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...