Description of Function Codes
I5300 User Manual
- 142 -
F
unction Code
Parameter Name
Setting Range
Default
P
0-08
Preset frequency
0.00 to maximum frequency (valid when
frequency source is digital setting)
50 Hz
If the frequency source is digital setting or terminal UP/DOWN, the value of this parameter
is the initial frequency of the AC drive (digital setting).
F
unction Code
Parameter Name
Setting Range
Default
P
0-09
Rotation direction
0: Same direction
1: Reverse direction
0
You can change the rotation direction of the motor just by modifying this parameter without
changing the motor wiring. Modifying this parameter is equivalent to exchanging any two of
the motor's U, V, W wires.
Note
The motor will resume running in the original direction after parameter initialization. Do not use
this function in applications where changing the rotating direction of the motor is prohibited after
system commissioning is complete.
F
unction Code
Parameter Name
Setting Range
Default
P
0-10
Maximum frequency
50.00–320.00 Hz
50.00 Hz
When the frequency source is AI, pulse setting (DI5), or multi-reference, 100% of the input
corresponds to the value of this parameter.
The output frequency of the I5300 can reach up to 3200 Hz. To take both frequency
reference resolution and frequency input range into consideration, you can set the number
of decimal places for frequency reference in P0-22.
•
If P0-22 is set to 1, the frequency reference resolution is 0.1 Hz. In this case, the
setting range of P0-10 is 50.0 to 3200.0 Hz.
•
If P0-22 is set to 2, the frequency reference resolution is 0.01 Hz. In this case, the
setting range of P0-10 is 50.00 to 320.00 Hz.
Note
After the value of
P
0-22 is modi
fi
ed, the frequency resolution of all frequency related function
codes change accordingly.
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...