Figure 6-28 PID parameters switchover
PID deviation
PI
parameters
Group 1 of PID
parameters
PA
-19
PA
-20
PA
-05,
PA
-06,
PA
-07
PA
-15,
PA
-16,
PA
-17
Group 2 of PID
parameters
F
unction Code
Parameter Name
Setting Range
Default
P
A-21
PID initial value
0.0%–100.0%
0.0%
P
A-22
PID initial value holding time
0.00–650.00s
0.00s
When the AC drive starts up, the PID starts closed-loop algorithm only after the PID output
is fxed to the PID initial value (PA-21) and lasts the time set in PA-22.
Figure 6-29 PID initial value function
Output
frequency
PID initial value
PA
-21
PID initial value
holding time PA
-22
Time
F
unction Code
Parameter Name
Setting Range
Default
P
A-23
Maximum deviation between two PID
outputs in forward direction
0.00%–100.00%
1.00%
P
A-24
Maximum deviation between two PID
outputs in reverse direction
0.00%–100.00%
1.00%
This function is used to limit the deviation between two PID outputs (2 ms per PID output) to
suppress the rapid change of PID output and stabilize the running of the AC drive.
PA-23 and PA-24 respectively correspond to the maximum absolute value of the output
deviation in forward direction and in reverse direction.
I5300 User Manual Description of Function Codes
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...