- 191 -
These two parameters are respectively used to set the detection value of output frequency
and hysteresis value upon cancellation of the output. The value of P8-20 is a percentage of
the hysteresis frequency to the frequency detection value (P8-19).
The FDT function is shown in the following figure.
Figure 6-17 FDT level
Time (t)
Output frequency (Hz)
FDT level
FDT hysteresis
=
P
8-19
x P
8-20
Time (t)
Frequency reached
detection signal
(DO, relay)
ON
F
unction Code
Parameter Name
Setting Range
Default
P
8-21
Detection range of frequency
reached
0.00–100% (maximum
frequency)
0.0%
If the AC drive running frequency is within the certain range of the set frequency, the
corresponding DO terminal becomes ON.
This parameter is used to set the range within which the output frequency is detected
to reach the set frequency. The value of this parameter is a percentage relative to the
maximum frequency. The detection range of frequency reached is shown in the following
figure.
Figure 6-18 Detection range of frequency reached
Time (t)
Output frequency (Hz)
Set frequency
Detection
range
Frequency reached
detection signal
ON
ON
I5300 User Manual Description of Function Codes
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...