Mechanical and Electrical Installation I5300 User Manual
- 30 -
Chapter 3 Mechanical and Electrical Installation
3.1 Mechanical Installation
3.1.1 Installation Environment Requirements
Item
Requirements
Ambient temperature
-10°C to +50°C
Heat dissipation
Install the AC drive on the surface of an incombustible object, and
ensure that there is suf
fi
cient space around for heat dissipation.
Install the AC drive vertically on the support using screws.
Mounting location
F
ree from direct sunlight, high humidity and condensation
F
ree from corrosive, explosive and combustible gas
F
ree from oil dirt, dust and metal powder
Vibration
Less than 0.6 g
F
ar away from the punching machine or the like
Protective enclosure
The I5300 series AC drives of plastic housing are the whole unit
built-in products operated through remote control and need to be
installed in the
fi
nal system.The
fi
nal system must have the required
fi
reproof cover, electrical protective cover and mechanical protective
cover, and satisfy the regional laws & regulations and related IEC
requirements.
3.1.2 Installation Clearance Requirements
The clearance that needs to be reserved varies with the power class of the I5300, as
shown in the following figure.
Figure 3-1 Clearance around the I5300 for installation
The AC drive shall be installed vertically upward .
B
B
A
A
Hot air
Cold air
0.7
−
15 kW
A
≥
10 mm
B ≥
100 mm
18.5
−
22 kW
A
≥
10 mm
B ≥
200 mm
22
−
37 kW
A
≥
50 mm
B ≥
200 mm
37
−
90 kW
A
≥
50 mm
B ≥
300 mm
Installation clearance requirements on
the I5300 series AC drives of different
power classes
Power Class
Clearance Requirements
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...