Mechanical and Electrical Installation ÿÿI5300 User Manual
- 36 -
■
Description of Main Circuit Terminals of Three-phase AC drive
R
S
T
PB
U
V
W
POWER
MOTOR
Table 3-1 Description of main circuit terminals of three-phase AC drive
Terminal
Name
Description
R, S, T
Three-phase power supply
input terminals
Connect to the three-phase AC power supply
(+), (-)
Positive and negative
terminals of DC bus
Common DC bus input point
Connect the external braking unit to the AC drive of
37 kW and above.
(+), P
B
Connecting terminals of
braking resistor
Connect to the braking resistor for the AC drive of
30 kW and below.
P, (+)
Connecting terminals of
external reactor
Connect to an external reactor.
U, V, W
AC drive output terminals
Connect to a three-phase motor.
Grounding terminal
Must be grounded.