Maintenance and Troubleshooting
I5300 User Manual
- 268 -
F
ault Name
Display
Possible Causes
Solutions
Pulse-by-pulse
current limit fault
Err40
1: The load is too heavy or locked-
rotor occurs on the motor.
2: The AC drive model is of too
small power class.
1: Reduce the load and
check the motor and
mechanical condition.
2: Select an AC drive of
higher power class.
Motor switchover
fault during
running
Err41
Change the selection of the motor
via terminal during running of the
AC drive.
Perform motor switchover
after the AC drive stops.
Too large speed
deviation
Err42
1: The encoder parameters are set
incorrectly.
2: The motor auto-tuning is not
performed.
3:
P
9-69 and
P
9-70 are set
incorrectly.
1: Set the encoder
parameters properly.
2: Perform the motor auto-
tuning.
3: Set
P
9-69 and
P
9-70
correctly based on the actual
situation.
Motor over-speed
Err43
1: The encoder parameters are set
incorrectly.
2: The motor auto-tuning is not
performed.3:
P
9-69 and
P
9-70 are
set incorrectly.
1: Set the encoder
parameters properly.
2: Perform the motor auto-
tuning.
3: Set
P
9-69 and
P
9-70
correctly based on the actual
situation.
Motor overheat
Err45
1: The cabling of the temperature
sensor becomes loose.
2: The motor temperature is too high.
1: Check the temperature
sensor cabling and eliminate
the cabling fault.
2: Lower the carrier
frequency or adopt other
heat radiation measures.
Initial position
fault
Err51
The motor parameters are not set
based on the actual situation.
Check that the motor
parameters are set correctly
and whether the setting of
rated current is too small.
9.4 Common
F
aults and Solutions
You may come across the following faults during the use of the AC drive. Refer to the
following table for simple fault analysis.
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...