- 147 -
F
unction Code
Parameter Name
Setting Range
Default
P
0-25
Acceleration/Deceleration
time base frequency
0: Maximum frequency (
P
0-10)
1: Set frequency
2: 100 Hz
0
The acceleration/deceleration time indicates the time for the AC drive to increase from 0
Hz to the frequency set in P0-25. If this parameter is set to 1, the acceleration/deceleration
time is related to the set frequency. If the set frequency changes frequently, the motor's
acceleration/deceleration also changes.
F
unction Code
Parameter Name
Setting Range
Default
P
0-26
B
ase frequency for UP/DOWN
modi
fi
cation during running
0: Running frequency
1: Set frequency
0
This parameter is valid only when the frequency source is digital setting.
It is used to set the base frequency to be modified by using keys
and
or the
terminal UP/DOWN function. If the running frequency and set frequency are different, there
will be a large difference between the AC drive's performance during the acceleration/
deceleration process.
F
unction Code
Parameter Name
Setting Range
Default
P
0-27
B
inding command
source to
frequency source
Unit's digit (
B
inding operation panel
command to frequency source)
000
0: No binding
1:
F
requency source by digital setting
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
Ten's digit (
B
inding terminal command to
frequency source)
0–9, same as unit's digit
Hundred's digit (
B
inding communication
command to frequency source)
0–9, same as unit's digit)
It is used to bind the three running command sources with the nine frequency sources,
facilitating to implement synchronous switchover.
For details on the frequency sources, see the description of P0-03 (Main frequency source X
selection). Different running command sources can be bound to the same frequency source.
I5300 User Manual Description of Function Codes
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...