- 239 -
Group AC: AI/AO Correction
F
unction Code
Parameter Name
Setting Range
Default
AC-00
AI1 measured voltage 1
0.500–4.000 V
F
actory-corrected
AC-01
AI1 displayed voltage 1
0.500–4.000 V
F
actory-corrected
AC-02
AI1 measured voltage 2
6.000–9.999 V
F
actory-corrected
AC-03
AI1 displayed voltage 2
6.000–9.999 V
F
actory-corrected
AC-04
AI2 measured voltage 1
0.500–4.000 V
F
actory-corrected
AC-05
AI2 displayed voltage 1
0.500–4.000 V
F
actory-corrected
AC-06
AI2 measured voltage 2
6.000–9.999 V
F
actory-corrected
AC-07
AI2 displayed voltage 2
9.999–10.000 V
F
actory-corrected
AC-08
AI3 measured voltage 1
9.999–10.000 V
F
actory-corrected
AC-09
AI3 displayed voltage 1
9.999–10.000 V
F
actory-corrected
AC-10
AI3 measured voltage 2
9.999–10.000 V
F
actory-corrected
AC-11
AI3 displayed voltage 2
9.999–10.000 V
F
actory-corrected
These parameters are used to correct the AI to eliminate the impact of AI zero offset and
gain.
They have been corrected upon delivery. When you resume the factory values, these
parameters will be restored to the factory-corrected values. Generally, you need not perform
correction in the applications.
Measured voltage indicates the actual output voltage value measured by instruments such
as the multimeter. Displayed voltage indicates the voltage display value sampled by the AC
drive. For details, refer to U0-21, U0-22 and U0-23.
During correction, send two voltage values to each AI terminal, and save the measured
values and displayed values to the function codes AC-00 to AC-11. Then the AC drive will
automatically perform AI zero offset and gain correction.
If the input voltage and the actual voltage sampled by the AC drive are inconsistent, perform
correction on site. Take AI1 as an example. The on-site correction is as follows:
1) Send a voltage signal (approximately 2 V) to AI1.
2) Measure the AI1 voltage and save it to AC-00.
3) View the displayed value of U0-21 and save the value to AC-01.
4) Send a voltage signal (approximately 8 V) to AI1.
5) Measure AI1 voltage and save it to AC-02.
6) View the displayed value of U0-21 and save the value to AC-03.
At correction of AI2 and AI3, the actually sampled voltage is respectively queried in U0-22
and U0-23.
For AI1 and AI2, 2 V and 8 V are suggested as the correction voltages. For AI3, -8 V and 8
V are suggested.
I5300 User Manual Description of Function Codes
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...