- 161 -
Group
P
4: Input Terminals
The I5300 provides fve DI terminals (DI5 can be used for high-speed pulse input) and two
analog input (AI) terminals. The optional extension card provides another five DI terminals
(DI6 to DI10) and an AI terminal (AI3).
F
unction Code
Parameter Name
Default
Remark
P
4-00
DI1 function selection
1:
F
orward RUN (
F
WD)
Standard
P
4-01
DI2 function selection
4:
F
orward JOG (
F
JOG)
Standard
P
4-02
DI3 function selection
9:
F
ault reset (RESET)
Standard
P
4-03
DI4 function selection
12: Multi-reference terminal 1
Standard
P
4-04
DI5 function selection
13: Multi-reference terminal 2
Standard
P
4-05
DI6 function selection
0
Extended
P
4-06
DI7 function selection
0
Extended
P
4-07
DI8 function selection
0
Extended
P
4-08
DI9 function selection
0
Extended
P
4-09
DI10 function selection
0
Extended
The following table lists the functions available for the DI terminals.
Table 6-1 Functions of DI terminals
Value
F
unction
Description
0
No function
Set 0 for reserved terminals to avoid malfunction.
1
F
orward RUN (
F
WD)
The terminal is used to control forward or reverse RUN
of the AC drive.
2
Reverse RUN (REV)
3
Three-line control
The terminal determines three-line control of the AC
drive.
F
or details, see the description of
P
4-11.
4
F
orward JOG (
F
JOG)
F
JOG indicates forward JOG running, while RJOG
indicates reverse JOG running. The JOG frequency,
acceleration time and deceleration time are described
respectively in
P
8-00,
P
8-01 and
P
8-02.
5
Reverse JOG (RJOG)
6
Terminal UP
If the frequency is determined by external terminals, the
terminals with the two functions are used as increment
and decrement commands for frequency modi
fi
cation.
When the frequency source is digital setting, they are
used to adjust the frequency.
7
Terminal DOWN
8
Coast to stop
The AC drive blocks its output, the motor coasts to rest
and is not controlled by the AC drive. It is the same as
coast to stop described in
P
6-10.
9
F
ault reset (RESET)
The terminal is used for fault reset function, the same
as the function of RESET key on the operation panel.
Remote fault reset is implemented by this function.
I5300 User Manual Description of Function Codes
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...