The switch signal mode is set in P4-11. The input terminal of the start/stop signal is set
in P4-00 to P4-09. For details, see the description of F4-11 and P4-00 to P4-09.
Example 1:
To use the DIP switch as the start/stop source, and allocate the forward rotation switch
signal to DI2 and the reverse rotation switch signal to DI3, perform the setting as shown
in the following figure.
Figure 4-6 Setting of using the DIP switch for start/stop
P
4-00
P
4-01
P
4-02
P
4-03
P
4-04
.
.
1
2
.
.
P
0-02 = 1
Running
command
P
4-11 = 0
Control switch
Terminal
Function
code
Setting
value
Terminal
control
DI1
DI2
DI3
DI4
DI5
.
COM
RUN/
Forward
Forward RUN
Terminal control
Command source
selection
Two-line mode 1
RUN/
Reverse
Reverse RUN
SW2
SW1
In the preceding figure, when SW1 is ON, the AC drive instructs forward rotation; when
SW1 is OFF, the AC drive stops. When SW2 is ON, the AC drive instructs reverse
running; when SW2 is OFF, the AC drive stops. If SW1 and SW2 are ON or OFF
simultaneously, the AC drive stops.
Example 2:
To use the electromagnetic button as the start/stop source, and allocate the startup
signal to DI2, stop signal to DI3 and reverse rotation signal to DI4, perform the setting
as shown in the following figure.
Figure 4-7 Setting of using the electromagnetic button for start/stop
P
4-00
P
4-01
P
4-02
P
4-03
P
4-04
.
.
1
2
3
.
P
0-02 = 1
Running
command
P
4-11 = 2
Control
button
Terminal
Function
code
Setting
value
Terminal
control
DI1
DI2
DI3
DI4
DI5
.
COM
RUN/
Forward
STOP
Forward RUN
Stop
Terminal control
Command
source selection
Three-line mode 1
RUN/
Reverse
Reverse RUN
SB
2
SB
1
SB
3
In the preceding figure, SB1 must stay ON during normal start and running. The AC
drive stops immediately after SB1 becomes OFF. The signals from SB2 and SB3
become valid once they become ON. The running state of the AC drive is determined
by the final actions on the three buttons.
Summary of Contents for I5300 Series
Page 8: ......
Page 9: ...1 Safety Information and Precautions ...
Page 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Page 17: ...2 Product Information ...
Page 28: ...Product Information I5300 User Manual 28 ...
Page 29: ...3 Mechanical and Electrical Installation ...
Page 45: ...4 Operation Display and Application Examples ...
Page 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Page 79: ...5 Function Code Table ...
Page 135: ...6 Description of Function Codes ...
Page 247: ...7 EMC ...
Page 255: ...8 Selection and Dimensions ...
Page 261: ...9 Maintenance and Troubleshooting ...