Posit
ion
Name
Add
ress
DIP Switch ID
1
2
3
4
5
6
Hot aisle 3 temp/
humid
23
ON
ON
ON
OFF
ON
OFF
Hot aisle 4 temp/
humid
24
OFF
OFF
OFF
ON
ON
OFF
Hot aisle 5 temp/
humid
25
ON
OFF
OFF
ON
ON
OFF
NO TICE
After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
----End
3.12.7 (Optional) Installing a Micro Differential Pressure
Sensor
Procedure
Step 1 Secure the micro differential pressure sensor and sheet metal to the cabinet using
M5 tapping screws.
Figure 3-70 Securing a differential pressure sensor (NetCol5000-C065)
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
3 Installation
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
80