Figure 7-18 Setting alarm parameter 2
----End
7.1.14 How Do I Commission a Component?
Context
●
On the diagnostic mode screen, you can turn on or off components, and
control their output ratio.
●
If you need to manually turn on or off system components in diagnostic
mode, ensure that the smart cooling product is started before operation.
●
The following describes how to commission an indoor fan.
Procedure
Step 1 Choose Maint > Diagnostic Mode > Enter.
NO TE
On the screen for entering the diagnostic mode:
● Components are interlocked. Therefore, buttons for turning on or off certain
components are in gray, indicating that operations of the components are not allowed.
● To ensure system security, a component may not promptly respond to operations
performed on this screen. For example, the compressor does not respond promptly after
the Off (On) button is tapped if the shortest running (shutdown) time is not met.
● To exit the diagnostic mode, tap
on the status bar.
● The system automatically exits diagnostic mode when it reaches the maximum
diagnostic mode duration.
Step 2 Set Indoor fan to 50%.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
7 FAQ
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
187