Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A093-01
High humidity alarm
Warning
● The thermal load is
low.
● The ambient
humidity exceeds
the upper
threshold.
● The temperature
and humidity
sensor is not
installed in a
proper position.
● The high humidity
alarm threshold is
inappropriate.
● The value detected
by the temperature
and humidity
sensor is different
from the actual
value.
1. Contact Huawei
technical support.
2. Measure the
ambient humidity.
3. Adjust the position
of the temperature
and humidity
sensor.
4. Adjust the high
humidity alarm
threshold.
5. Calibrate or replace
the temperature
and humidity
sensor.
A094-01
Low humidity alarm
Warning
● The ambient
humidity is below
the lower
threshold.
● The temperature
and humidity
sensor is not
installed in a
proper position.
● The low humidity
alarm threshold is
inappropriate.
● The value detected
by the temperature
and humidity
sensor is different
from the actual
value.
1. Measure the
ambient humidity.
2. Adjust the position
of the temperature
and humidity
sensor.
3. Adjust the low
humidity alarm
threshold.
4. Calibrate or replace
the temperature
and humidity
sensor.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
6 System Operation and Maintenance
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
145