Item
NetCol5000-C065
a: Rated working conditions are that the return air temperature is 37°C; the
return air relative humidity is 24%; the supply/return water temperatures are
10°C/15°C respectively; and the static pressure outside the smart cooling
product is 0 Pa.
2.9 Technical Specifications (NetCol5000-C030/C032)
Table 2-6 Technical specifications of NetCol5000-C030/C032
Item
NetCol5000-C030
NetCol5000-C032
Power system
220 V AC to 240 V AC 1 Ph 50/60
Hz, dual power supplies
220 V AC to 240 V AC 1 Ph
50/60 Hz, dual power
supplies
Tolerance
Rated voltage –15% to +10%,
rated frequency ±5 Hz
Rated voltage –15% to
+10%, rated frequency ±5
Hz
Number of
fans
6
6
Cooling
capacity (kW)
30
a
32
a
Air volume
(m
3
/h)
5400
5400
Maximum
operating
current (A)
9.5
9.5
Maximum
operating
pressure
(MPa)
1.6
1.6
Humidificatio
n
● NetCol5000-C030H90D0: No
● NetCol5000-C030H9HD0: Yes
● NetCol5000-C030H9HE0: Yes
NetCol5000-C032H9HD0:
Yes
Humidificatio
n capacity
(kg/h)
● NetCol5000-C030H90D0: 0
● NetCol5000-C030H9HD0: 1.5
● NetCol5000-C030H9HE0: 1.5
NetCol5000-C032H9HD0:
1.5
External
dimensions (H
x W x D)
2000 mm x 300 mm x 1200 mm
2200 mm x 300 mm x
1200 mm
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
2 Product Description
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
28