Figure 3-6 Connecting a humidifier water inlet pipe
(1) Connector with outer screw
threads: G 3/4 inch
(2) Adapter with inner screw
threads: G 3/4 inch. Plastic
materials such as PA66 and
metal materials are
recommended.
(3) Matched with the adapter,
the pressure resistance should
be at least 0.7 MPa
NO TE
The object shown in the dotted line box is the water inlet pipe connector with outer screw
threads delivered with smart cooling products. Other parts are not provided and need to be
purchased.
3.1.2.4 Chilled Water Inlet and Outlet Pipes
The following illustrates how to connect water inlet and outlet pipes to reserved
ports on the cabinet.
Figure 3-7 Connecting the water inlet and outlet pipes
(1) NetCol5000-C065: G 1–1/2 in. port with
inner threads (reserved device port)
NetCol5000-C030/C032: G 1 in. port with inner
threads (reserved device port)
(2) NetCol5000-C065: Seamless steel pipe with
a G 1–1/2 in. external threaded connector
(engineering purchase)
NetCol5000-C030/C032: Seamless steel pipe
with a G 1 in. external threaded connector
(engineering purchase)
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
3 Installation
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
37