Configurations of temperature and humidity alarms and main board alarms for
the air cooled devices comply with the following relationships:
●
Power underfrequency alarm threshold < Power overfrequency alarm
threshold
●
Backup power underfrequency alarm threshold < Backup power
overfrequency alarm threshold
●
Supply air high temperature alarm thr 5°C ≤ Return air high
temperature alarm threshold
●
Supply air high temperature alarm thr 5°C ≤ Hot aisle high
temperature alarm threshold
●
Cold aisle high temperature alarm thr 5°C ≤ Hot aisle high
temperature alarm threshold
●
Cold aisle high temperature alarm thr 5°C ≤ Return air high
temperature alarm threshold
●
Supply air low temperature alarm thr 5°C ≤ Return air low
temperature alarm threshold
Context
●
To set an alarm threshold, follow the instructions in this section.
●
The method for setting each alarm is the same. This section describes how to
set Threshold of Supply air high temperature alarm to 45.
●
If you need to change alarm settings, log in as the Admin user.
NO TICE
Be careful when configuring alarms. Only professional maintenance personnel can
change alarm settings.
Procedure
Step 1 Choose Settings > Alarm Settings > T/H Sensor on the home screen.
is displayed.
Figure 7-17 Setting alarm parameter 1
Step 2 Tap Threshold following Supply air high temperature alarm.
Step 3 Set the value to 45 and tap
, as shown in
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual