296
Type: 2K
Cooling in the 4-pipe system
There is a separate coil for heating and for cooling. The
DigiNet system is switched between heating and cooling
automatically. Two switch relays and the additional terminals
for enable cooling and the trouble input cooling are installed
in the zone control panel.
Type: 4K
Room temperature average value
Instead of only 1 room air sensor, 4 sensors are provided to
determine the average value; the corresponding terminals
are integrated.
Type: MRT
DigiPlus controller
The DigiPlus controller is installed in the zone control panel
in addition to the DigiZone controller. It enables the following
additional functions:
■
Humidity control: Depending on the relative humidity of
the room air, DigiNet gives an output signal (DC 0…10 V)
to control humidity equipment. (Required: humidity sensor,
built-in humidity equipment)
■
Ventilation according to requirements: The speed of
the fans and therefore the air change speed is varied
according to the CO
2
concentration in the room.
(Required: Fans with variable volume flow, CO
2
sensor)
■
External control of volume flow: Fans with a variable
volume flow (option) can be controlled by an external
signal (DC 0...10 V).
■
Cascading electro coils: The DigiPlus controller switches
up to three 2-level electro coils for each control zone
depending on the analog heating valve output.
Type: DP5
Humidity sensor
The sensor measures the relative humidity in the room air as
a basis for humidity control. It is installed on the wall in the
occupied area, at a height of about 1.5 m.
Type
FF
Measurement range
0…100 %
Output signal
DC 0…10 V
Table L19: Technical data for the humidity sensor
CO
2
sensor
The sensor measures the CO
2
concentration in the room air
as a basis for ventilation as required. It is installed on the
wall in the occupied area, at a height of about 1.5 m.
Type
CO
2
Measurement range
0…2000 ppm
Output signal
DC 0…10 V
Table L20: Technical data for the CO
2
sensor
Base for the zone control panel
Zone control panels in sizes 7 to 9 are available with a sheet
steel base, height 200 mm.
Type: SO
Control systems
Options
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......