1 General information
Hoval's DigiNet is a control system that was specially devel-
oped for decentralised indoor climate units. The system was
developed together with Sauter AG, a company which also
supplies the hardware components.
2 System setup
Hoval's DigiNet is divided into three hierarchical levels
connected by a novaNet system bus.
2.1 Operator level
This is where the user operates the system. Different opera-
tional options are available according to project-specific
requirements.
2.2 Zone level
Indoor climate units that operate under the same conditions
are summarised into control zones. Criteria for the creation of
a zone can be, for example, operating times, room tempera-
ture set values and so on. In the zone control panel, there is
a DigiZone controller for each control zone. It switches the
operating modes of the units according to the scheduler.
Different unit types can also be combined in a control zone. A
distinction is made between:
■
Main units (= fresh air units or supply air units)
■
Additional units (= recirculation units that are switched on
if there is a heat or cool demand).
A DigiEco controller is installed in the zone control panel for
additional units.
Control zones
max. 10
Main units in each control zone
max. 9
Additional units in each control zone max. 9
Table L1: Application limits of the Hoval DigiNet
Note
Special solutions are possible for larger projects.
2.3 Unit level
A DigiUnit controller is installed in each main unit (= fresh
air unit or supply air unit). This controls the unit individually
according to local conditions.
2.4 novaNet system bus
The individual Hoval DigiNet components are connected via
a novaNet system bus (analogously to the OSI layer model)
Data transfer takes place in an event-oriented manner, this
reduces data traffic and ensures short reaction times.
novaNet system bus
Cable type
1 pair of wires, drilled,
shielded
category 5 or above
Topology
in series
Length
Max. 1900 m
For longer bus lengths: Include a
repeater or divide the system into
several networks.
Communication
Cross-communication with equal
priority (peer-to-peer / multiplier)
Loop resistance
max. 300
Ω
Capacity
max. 200 nF
Table L2: novaNet system bus specification
Example – bus cable
Type
_______________________
G51
Dimension (n x n x mm²)
_______
1 x 2 x 0.8
Loop resistance at 20 °C
_______
37.5
Ω
/km
Operating capacity
____________
60 nF/km
Application
__________________
Category 5e / class D
Features
___________________
drilled, halogen-free
Control systems
General information
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......