292
Design
Control panel
Coated sheet steel (RAL No.
7035)
Short circuit resistance I
CW
10 kA
eff
Connecting terminals
Top
Installation
Floor or wall installation
Ambient conditions
Use
Indoors
Ambient temperature
5…40 °C
Storage and transport
temperature
- 25…55 °C
Ambient humidity
max. 50 % rh at 40 °C
max. 90 % rh at 20 °C
Table L7: Technical data for the zone control panel
Enable heating/cooling
Floating signal that reports the
heat-/cool demand to the heat
generation and refrigeration units
on-site
3 x 1.5 mm²
max. AC 230 V, 2 A
Trouble input heating/cooling
Alarm input signal that informs the
DigiNet that the heat-/cold supply
is not working
3 x 1.5 mm²
AC 24 V
Collective trouble indicator
Floating signal for the external
display of a collective alarm
3 x 1.5 mm²
max. AC 230 V, 6 A
Table L8: External connections
Size
Type
Dimensions in mm (W x H x
D)
1
SDZ1
380 x
600 x
210
2
SDZ2
600 x
600 x
210
3
SDZ3
600 x
760 x
210
4
SDZ4
760 x
760 x
210
5
SDZ5
800 x
1000 x
300
6
SDZ6
800 x
1200 x
300
7
SDZ7
800 x
1800 x
400
8
SDZ8
1000 x
1800 x
400
9
SDZ9
1200 x
1800 x
400
Table L9: Available sizes and dimensions for the zone control panel
Control systems
Zone control panel
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......