301
B
E
E
F
G
H
I
J
K
L
M
N
2 Location of the temperature sensors
2.1 Room air sensor
Install the sensor at a height of about 1.5 m in a representa-
tive location in the occupied area. Its measured values must
not be distorted by the presence of sources of heat or cold
(machines, direct sunlight, windows, doors, etc.).
Normally, you should use one room air sensor for each
control zone. It is also possible to install four sensors to
determine the average temperature value.
2.2 Fresh air sensor
Install the sensor at least 3 m above the ground on a
north-facing wall, so that it is protected from direct sunlight.
Provide additional cover for the sensor and thermally insulate
it from the building.
Only one fresh air sensor is needed per system.
Extract air and supply air sensors are installed in the
RoofVent
®
units.
3 Orientation of the coil connections
The heating or cooling section is usually fitted to the filter box
in such a way that the coil connections are underneath the
extract air grille (see Fig. M5). Check the local installation
conditions. If a different orientation is required, please specify
on the purchase order.
Fig. M5: Orientation of
the coil connections
Fig. M4: Conceptual drawing
T
U
Load-bearing outside wall of the roof frame, position as
centrally as possible on IPE beams
Insulation (e.g. 40 mm PU foam)
IPE beam
Unit size
6
9
10
T
Max.
mm
1000
1240
1240
U
Min.
mm
914
1154
1154
Table M1: Dimensions for roof frame
System design
Location of the temperature sensors
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......