11 Fresh air silencer
The fresh air silencer reduces the noise from RoofVent
®
units
through the weather louvre door. It consists of an Aluzinc
cowl with sound attenuation lining and an opening in down-
ward direction. The silencer is connected by hinges to the
top edge of the unit. Please note the following:
■
Using a fresh air silencer only makes sense in combina-
tion with an exhaust air silencer of type FSD-6/110 or
FSD-9-10/110.
■
In RoofVent
®
LH and LK units, additional sound attenua-
tion splitters are installed in the fresh air chamber.
Type
ASD-6
ASD-9-10
L
mm
500
600
W
mm
1080
1380
H
mm
790
825
Weight
kg
44
70
Pressure drop
Pa
4
4
Table K17: Technical data for the fresh air silencer
Frequency
ASD-6 ASD-9-10
63 Hz
-1
0
125 Hz
1
2
250 Hz
5
5
500 Hz
5
6
1000 Hz
6
6
2000 Hz
5
6
4000 Hz
6
5
8000 Hz
4
5
Sum
5
5
Table K18: Insertion attenuation of the fresh air silencer (values in dB at standard fan
speed)
12 Exhaust air silencer
The exhaust air silencer reduces the noise from RoofVent
®
units through the exhaust air grille. It consists of an Aluzinc
casing with sound attenuation splitters. Please note the
following:
■
The exhaust air flow rate is slightly reduced by the addi-
tional pressure drop.
■
The exhaust air silencer is available in two different
lengths.
■
The exhaust air silencer is delivered in dismantled form;
please follow the assembly instructions.
Type FSD-
6/60
6/110 9-10/60 9-10/110
L
mm
600
1100
600
1100
W
mm
1080
1080
1380
1380
H
mm
790
790
825
825
Weight
kg
120
185
125
205
Pressure drop Pa
15
20
20
25
Table K19: Technical data for the exhaust air silencer
Frequency FSD-
6/60
6/110 9-10/60 9-10/110
63 Hz
4
8
6
9
125 Hz
5
9
8
12
250 Hz
9
14
11
17
500 Hz
15
22
15
22
1000 Hz
20
26
17
24
2000 Hz
19
25
19
25
4000 Hz
19
25
15
23
8000 Hz
14
22
11
17
Sum
11
16
13
18
Table K20: Insertion attenuation of the exhaust air silencer (values in dB at standard
fan speed)
Options
Fresh air silencer
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......