3.2 Application limits
Extract air temperature
max.
50 °C
Extract air relative humidity
max.
60 %
Moisture content of extract air
1)
max.
9.5 g/kg
Fresh air temperature
Heating
-20…+15 °C
Cooling
-5…+43 °C
Supply air temperature
max.
60 °C
Minimum operating time VE2
min.
30 min
Amount of condensate
max.
150 kg/h
Air flow rate
min.
5000 m³/h
1)
If the ambient humidity increases by more than 2 g/kg, a drop eliminator for the plate heat exchanger
and an extract air filter in front of the extract air grille must be installed.
Table F3: Application limits of the RoofVent
®
twin pump
Caution
Danger of damage to the unit as a result of condensate. At high humidity
levels or extremely low fresh air temperatures, humidity in the extract air
may condense in plate heat exchanger 1. Use the drop eliminator (option)
to ensure that no condensate can drip into the unit.
RoofVent
®
twin pump
Technical data