244
3.3 Air flow rate, electrical connections
Unit type
LK-6
LK-9
Air distribution
Nominal air flow rate
1)
Supply air m³/h
5000
7650
Exhaust air m³/h
5000
7650
Floor area reached
Max.
m²
484
729
Fan characteristics
Supply voltage
V AC
3 x 400
3 x 400
Permitted voltage tolerance
%
± 10
± 10
Frequency
Hz
50
50
Active power per motor
kW
1.8
3.0
Current consumption
A
4.0
6.5
Set point of thermal relays
A
4.6
7.5
Speed of rotation (nominal)
rpm
1440
1435
Actuators
Supply voltage
V AC
24
24
Frequency
Hz
50
50
Control voltage
V DC
2…10
2…10
Torque
Nm
10
10
Run time for 90° rotation
s
150
150
Filter monitoring
Factory setting of differential pressure switches Pa
300
300
1)
Refers to: RoofVent
®
LK with heating/cooling coil type C and vertical supply air discharge direction
Table J4: Technical data, RoofVent
®
LK
RoofVent
®
LK
Technical data
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......