3.4 Technical data for the heat pump
Unit type
ERQ250
Nominal heat output
1)
kW
31.5
Nominal cooling capacity
2)
kW
28.0
Control range
%
0…100
Working medium
–
R410a
Working medium filling quantity (pre-filled)
kg
8.4
Evaporation temperature
°C
5.0
Sound pressure level (at a distance of 5 m)
3)
dB (A)
58
Sound power level
4)
dB (A)
78
Supply voltage
V AC
3 x 400
Frequency
Hz
50
Power consumption max.
kW
7.70
Current consumption max.
A
11.3
COP value
–
4.09
EER
–
3.77
Starting current
A
74
1)
at fresh air temperature 7 °C / extract air temperature 20 °C
2)
at fresh air temperature 35 °C / extract air temperature 27 °C / 45 % rel. humidity
3)
with hemispherical radiation in a low-reflection environment
4)
The specified values are maximum values; the noise level fluctuates due to scroll technology.
Table F5: Technical data for the Daikin heat pump
RoofVent
®
twin pump
Technical data