146
8.4 Air-Injector D
Internally-insulated Aluzinc sheet steel casing with:
■
Vortex air distributor with concentric outlet nozzle, adjust-
able vanes and integrated absorber hood
■
Actuator for automatic adjustment of the air distribution
■
Supply air sensor
■
Electric connection box (includes the terminals for the
heating/cooling mixing valve)
Type
D -9
Floor area reached
…
m²
8.5 Heat pump
Daikin ERQ250A7W1B
Modulating air/air heat pump system for heating and cooling,
as a split system
■
Compact unit for outdoor installation
■
Painted casing RAL 7044 (silk grey) made from galva-
nised sheet steel
■
Speed-controlled scroll compressor
■
Speed-controlled fan
■
Coated Al/Cu finned-tube evaporator
■
Electronic expansion valve
■
4-way valve for defrosting
■
Shut-off valves on the working-medium side
■
Working medium R 410A
■
Terminal box
Type
Daikin ERQ250A7W1B
Max. heat output
31.5
kW
Cooling capacity max.
28.0
kW
Modulation range
0…100
%
Supply voltage
3 x 400
V AC
Frequency
50
Hz
8.6 Options
Hygiene design
■
Fresh air filter class F7
■
Extract air filter class F5
Fresh air silencer ASD
As an attachment to the weather louvre door, casing
consisting of Aluzinc sheet steel with lining of sound attenu-
ation material, for reducing noise from the weather louvre
door, insertion attenuation _____ dB
Exhaust air silencer FSD
As an attachment to the exhaust air grille, casing consisting
of Aluzinc sheet steel with built in sound attenuation splitters,
for reducing the noise from the exhaust air grille, insertion
attenuation _____ dB
Supply air silencer ZSD
As an inserted component in the below-roof unit, casing
consisting of Aluzinc sheet steel with built in sound attenu-
ation splitters, for reducing the noise in the room, insertion
attenuation _____ dB
Extract air silencer ABSD
As an attachment to the extract air grille, casing consisting
of Aluzinc sheet steel with built in sound attenuation split-
ters, for reducing the noise in the room, insertion attenuation
_____ dB
Acoustic cowl AHD
Consisting of an absorber hood of large volume and a screen
with a lining of sound attenuation material, insertion attenua-
tion 4 dB
Air outlet box AK
Made of Aluzinc sheet steel, with 4 adjustable exhaust air
grilles (replaces the Air-Injector)
Extract air filter in front of the extract air grille AF
As an attachment to the extract air grille, casing consisting of
Aluzinc sheet steel with inserted minipleat filter (class G4)
Drop eliminator TA
Consisting of aluminium fins, fitted in the extract air flow
on the air inlet side of the plate heat exchanger, to drain
condensate onto the roof
Condensate pump KP
Consisting of a centrifugal pump and a drip tray, max.
delivery rate of 150 l/h with a delivery head of 3 m
8.7 Control systems
Digital control system for the energy-optimised operation of
decentralised indoor climate systems:
■
System set up according to OSI reference model
■
Onsite connection to the individual control modules using
novaNet system bus in a serial topology
■
Cross-communication with equal priority (peer-to-peer/
multiplier) using novaNet log
■
Fast reaction times due to data transmission on an events
basis
■
Control modules pre-addressed in the factory with
integrated lightning protection and battery-buffered RAM
modules
■
No onsite engineering (binding) required
RoofVent
®
twin pump
Specification texts
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......