280
15 Acoustic cowl
The acoustic cowl reduces the noise level in the room; it is
installed in the Air-Injector. This does not change the outside
dimensions of the Air-Injector.
The insertion attenuation amounts to 4 dB with respect to the
total sound level of the respective RoofVent
®
unit.
16 Actuators with spring return
In the event of a power failure, actuators with spring return
close the fresh air damper and, if there is one, the ER
damper, and thus protect the unit from frost. They are
installed in place of the standard actuators.
Type
SMF
Supply voltage
AC 24 V
Frequency
50 Hz
Input signal
DC 0…10 V
Torque
20 Nm
Run time of actuator
150 s
Run time of spring return
20 s
Table K25: Technical data for the actuators with spring return
Fig. K4: Actuator with spring return
17 Air outlet box
When using the RoofVent
®
units in low-roofed halls, the air
outlet box can be installed in place of the Air-Injector. This
reduces the minimum mounting height by 1 m compared to
the standard design.
The air outlet box has horizontal exhaust air grilles on all
sides. The vanes can be manually adjusted without tools to
adapt the air discharge angle to the local conditions.
Note
The air outlet box replaces the Air-Injector. The total
height of the unit is somewhat smaller; the weight is
approximately the same.
R
Q
Type
AK-6
AK-9/10
R
mm
900
1100
Q
mm
350
400
Weight
kg
36
53
Table K26: Dimensions and weights of the air outlet box
Options
Acoustic cowl
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......