4 Condensation lilmit
RoofVent
®
twin heat / twin cool / twin pump
At high humidity levels or extremely low fresh air tempera-
tures, humidity in the extract air may condense in plate heat
exchanger 2. Diagram M1 shows under what air conditions
condensation occurs. In applications where the condensation
limit is exceeded:
■
Connect the condensate drain connection in the combi
box to a condensate drainage system.
■
Where required, use a condensate pump to discharge
condensate through waste water pipes directly below the
ceiling or onto the roof.
■
Use the option drop eliminator for the plate heat
exchanger 1 in the roof unit.