144
Component
Description
Voltage
Cable
Option Comment
DigiUnit terminal
box
Power supply
3 x 400 V
5 x 6 mm²
novaNet system bus
2 x 0.16 mm²
For bus cable specifications,
see Section L, chap. 2.4
Switch-over heating/cooling
Volt-free
Max. 230 V
3 x 0.75 mm²
Communication
box
Communication line, heat
pump
1 x 2 x 0.75 mm²
Heat pump
Power supply
3 x 400 V
5 x 6 mm²
Zone control
panel
3-phase
Power supply
3 x 400 V
5 x … mm²
Depending on options
novaNet system bus
2 x 0.16 mm²
For bus cable specifications,
see Section L, chap. 2.4
Room air sensor
2 x 1.5 mm²
Max. 170 m
Shielded cable
Fresh air sensor
2 x 1.5 mm²
Max. 170 m
Collective trouble indicator
Volt-free
Max. 230 V
3 x 1.5 mm²
Max. 6 A
Special function on terminal
24 V
3 x 1.5 mm²
Per special function
Power supply for the
RoofVent
®
twin pump
3 x 400 V
5 x 6 mm²
Per RoofVent
®
twin pump
Power supply for heat pump
3 x 400 V
5 x 6 mm²
Per heat pump
CO
2
sensor
24 V
4 x 1.5 mm²
Max. 170 m
Variant:
Zone control
panel
1-phase
Power supply
1 x 230 V
3 x … mm²
Depending on options
novaNet system bus
2 x 0.16 mm²
For bus cable specifications,
see Section L, chap. 2.4
Room air sensor
2 x 1.5 mm²
Max. 170 m
Shielded cable
Fresh air sensor
2 x 1.5 mm²
Max. 170 m
Collective trouble indicator
Volt-free
Max. 230 V
3 x 1.5 mm²
Max. 6 A
Special function on terminal
24 V
3 x 1.5 mm²
Per special function
CO
2
sensor
24 V
4 x 1.5 mm²
Max. 170 m
Table F13: Cable list
RoofVent
®
twin pump
Transport and installation
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......