18
3.5 Heat output
Note
The performance data listed here applies to the most frequent design conditions. Use the
selection program 'HK-Select' to calculate the performance data for other design data. You can
download 'HK-Select' free of charge on the Internet.
Fresh air temperature
-5 °C
-15 °C
LPHW
Size
Type
Q
Q
TG
H
max
t
S
∆p
W
m
W
Q
Q
TG
H
max
t
S
∆p
W
m
W
°C
kW
kW
m
°C
kPa
l/h
kW
kW
m
°C
kPa
l/h
80/60
LHW-6
A
37
20
16.2
28
8 1569
39
16
18.3
26
8 1663
LHW-6
B
52
36
12.4
36
14 2228
55
33
13.0
34
16 2363
LHW-6
C
80
64
9.5
51
13 3447
85
63
9.6
50
15 3656
60/40
LHW-6
A
23
7
25.0
21
3
984
25
3
25.0
19
4 1079
LHW-6
B
32
16
18.1
26
6 1393
36
13
20.4
24
8 1530
LHW-6
C
51
35
12.6
36
6 2185
56
33
12.9
35
7 2395
80/60
LHW-9
A
59
39
14.7
32
7 2544
62
34
15.7
30
7 2678
LHW-9
B
75
55
12.5
37
10 3235
79
51
12.9
36
11 3407
LHW-9
C
116
96
9.7
52
10 4984
122
94
9.8
51
11 5248
60/40
LHW-9
A
37
16
22.5
24
3 1570
40
12
25.0
22
3 1706
LHW-9
B
46
26
17.8
27
5 1992
51
22
19.4
26
5 2167
LHW-9
C
73
52
12.8
36
5 3119
79
51
13.0
36
5 3385
80/60
LHW-10
A
74
46
23.5
24
10 3173
74
35
23.5
24
10 3173
LHW-10
B
83
55
14.3
35
12 3549
88
49
15.2
33
14 3778
LHW-10
C
129
101
10.8
50
12 5529
137
98
10.9
49
14 5887
60/40
LHW-10
A
50
22
25.0
16
5 2151
50
11
25.0
16
5 2151
LHW-10
B
52
24
21.5
25
6 2231
57
18
25.0
23
7 2465
LHW-10
C
82
54
14.4
35
6 3528
91
52
14.8
34
7 3888
Legend:
Type =
Type of heating coil
Q
=
Heat output
Q
TG
=
Output to cover fabric heat losses
H
max
=
Maximum mounting height
t
S
=
Supply air temperature
∆p
W
=
Water pressure drop
m
W
=
Water flow rate
Refers to:
Room air 18 °C, extract air 20 °C/40 % rel. humidity
Table B6: Heat output, RoofVent
®
LHW
Note
The output for coverage of the fabric heat losses (Q
TG
) allows for the ventilation heat requirement
(Q
V
) and the energy recovery output (Q
ER
) under the respective air conditions. It is calculated as
follows: Q
TG
= Q + Q
ER
– Q
V
RoofVent
®
LHW
Technical data
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......