24
4 Design example
Design data
■
Required fresh air flow rate or air change rate
■
Hall geometry (length, width, height)
■
Design fresh air temperature
■
Desired room temperature (in the occupied area)
■
Extract air conditions
1)
■
Fabric heat losses (portion to be covered by the
RoofVent
®
units)
■
Internal heat gains (machines, lighting, etc.)
■
Heating medium
1)
The extract air temperature is generally higher than the temperature in the
occupied area. This is the result of unavoidable temperature stratifica-
tion in high spaces, but is reduced to a minimum with the Air-Injector.
A temperature gradient of only 0.2 K per metre height can therefore be
assumed.
Example
Fresh air flow rate ......................................30'000 m³/h
Hall geometry (L x W x H) ...................... 52 x 45 x 9 m
Design fresh air temp. ......................................... -5 °C
Desired room temperature...................................18 °C
Extract air conditions ............................... 20 °C / 40 %
Fabric heat losses ........................................... 220 kW
Internal heat gains ............................................. 36 kW
Heating medium ................................. LPHW 80/60 °C
Room temperature:..............................................18 °C
Temperature gradient: .................................... 9 · 0.2 K
Extract air temperature: ....................................≈ 20 °C
Required number of units n
req
Based on the air flow rate per unit (see Table B4), select a
trial unit size. (Depending on the results of further calcula-
tions, repeat the layout design for another unit size if neces-
sary.)
n
req
= V
req
/ V
U
V
req
= required fresh air flow rate in m³/h
V
U
= air flow rate for the selected unit size in m³/h
Approximate selection: Unit size LHW-9
n
req
= 30'000 / 8'000
n
req
= 3.75
Select 4 LHW-9s.
Actual fresh air flow rate V (in m³/h)
V
= n · V
U
n
= Selected number of units
V = 4 · 8'000
V = 32'000 m³/h
Effective fabric heat losses Q
Teff
(in kW)
Q
Teff
= Q
T
– Q
M
Q
T
= fabric heat losses in kW
Q
M
= internal heat gains in kW
Use the following criteria for calculation of internal heat
gains (connected loads of machines and lighting): Operating
times, diversity, direct heat output through convection, indi-
rect heat output through radiation, etc.
Q
Teff
= 220 – 36
Q
Teff
= 184 kW
Necessary output to cover fabric heat losses per unit
Q
TG
(in kW)
Q
TG
= Q
Teff
/ n
Q
TG
= 184 / 4
Q
TG
= 46 kW
RoofVent
®
LHW
Design example
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......