3.4 Integration at management level with DigiBac
An automation station with BACnet communication card –
known as DigiBac – allows you to integrate the Hoval DigiNet
at management level. Communication takes place over
BACnet/IP on an Ethernet basis.
For detailed information on integration at management level,
contact Hoval customer service.
4 Zone control panel
Hoval indoor climate units are grouped into control zones,
which are controlled from the zone control panel. The
DigiZone controller:
■
controls operating modes,
■
transmits the fresh air and room temperature to the indi-
vidual units,
■
sets the output for enable heating or enable cooling and
the collective trouble indicator.
For each panel
1 fresh air sensor (cable length max. 170 m)
1 transformer 230 / 24 V
2 circuit breakers for transformer (1-pin)
1 relay
1 safety relay (2-pin, external)
Connecting terminals for:
■
Fresh air sensor
■
Mains supply
For each control zone
1 DigiZone controller
1 room air sensor (supplied)
1 relay
Connecting terminals for:
■
Room air sensor
■
Enable heating
■
Trouble input heating
■
Collective trouble indicator
■
novaNet system bus
Table L6: Contents of the zone control panel
Caution
Danger of electric shocks. Ensure that overcurrent
protection equipment is installed onsite for the mains
connection line.
Fig. L5: View of the inside of the zone control panel
Control systems
Zone control panel
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......