46
3.6 Cooling capacities
Cooling medium temperature
6/12 °C
8/14 °C
t
F
rh
F
Size
Type
Q
sen
Q
tot
Q
TG
t
S
∆p
W
m
W
m
C
Q
sen
Q
tot
Q
TG
t
S
∆p
W
m
W
m
C
°C
%
kW
kW
kW
°C kPa
l/h kg/h
kW
kW
kW
°C kPa
l/h kg/h
28
40
LKW-6
C
19
21
13
15
13 3065
3
17
17
11
16
8 2403
0
60
LKW-6
C
18
36
12
15
33 5084
24
16
29
10
17
23 4199
19
32
40
LKW-6
C
24
33
18
16
29 4761
13
22
27
16
17
20 3877
7
60
LKW-6
C
–
–
–
–
–
–
–
21
46
14
18
51 6529
35
28
40
LKW-9
C
29
32
20
15
11 4553
4
25
25
16
16
7 3618
0
LKW-9
D
36
42
27
12
14 6047
10
31
31
22
14
8 4448
0
60
LKW-9
C
27
54
19
15
28 7753
38
24
45
15
17
20 6396
29
LKW-9
D
35
70
26
12
35 10067
50
30
59
21
14
25 8405
40
32
40
LKW-9
C
37
51
28
16
26 7315
20
33
42
24
17
18 5960
12
LKW-9
D
45
66
36
13
32 9510
30
41
55
31
14
22 7848
21
60
LKW-9
C
35
79
26
17
57 11375
63
31
70
22
18
44 9979
55
LKW-9
D
44 102
35
13
69 14630
82
39
90
30
15
54 12941
72
28
40
LKW-10 C
32
34
21
15
12 4879
3
28
28
17
16
8 3959
0
LKW-10 D
40
46
29
12
16 6551
9
34
34
23
14
9 4906
0
60
LKW-10 C
30
58
19
16
32 8339
40
26
48
16
17
23 6891
31
LKW-10 D
38
76
28
13
41 10953
54
33
64
23
14
29 9157
43
32
40
LKW-10 C
40
54
29
16
29 7801
21
36
44
26
18
20 6357
12
LKW-10 D
50
72
39
13
36 10262
32
45
59
34
15
25 8466
21
60
LKW-10 C
37
85
27
17
64 12183
67
34
75
23
18
50 10691
58
LKW-10 D
48
111
37
13
79 15866
89
43
98
32
15
63 14036
78
Legend:
t
F
=
Temperature of the fresh air
rh
F
=
Relative humidity of the fresh air
Type =
Type of cooling coil
Q
sen
=
Sensible cooling capacity
Q
tot
=
Total cooling capacity
Q
TG
=
Output for coverage of fabric cooling losses (→ sensible cooling load)
t
S
=
Supply air temperature
∆p
W
=
Water pressure drop
m
W
=
Water flow rate
m
C
=
Amount of condensate
Refers to:
■
At fresh air temperature 28 °C: room air 22 °C, extract air 24 °C/50 % rel. humidity
■
At fresh air temperature 32 °C: room air 26 °C, extract air 28 °C/50 % rel. humidity
— These operating conditions are not permissible, because the maximum condensate quantity of 60 kg/h is exceeded.
Table C7: Cooling capacity, RoofVent
®
LKW
Note
The output for coverage of fabric cooling losses (Q
TG
) allows for the ventilation cooling require-
ment (Q
V
) and the output of the energy recovery
(Q
ER
) under the respective air conditions. It is
calculated as follows: Q
TG
= Q
sen
+ Q
ER
– Q
V
RoofVent
®
LKW
Technical data
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......