21
B
E
E
F
G
H
I
J
K
L
M
N
Unit type
LHW-6
LHW-9
LHW-10
Dimensions of
roof unit
A
mm
2100
2400
2400
B
mm
1080
1380
1380
C
mm
1390
1500
1500
D
mm
600
675
675
E
mm
1092
1392
1392
Dimensions of
below-roof unit
Filter box design
F00
F25
F50
F00
F25
F50
F00
F25
F50
G
mm
940 1190 1440
980 1230 1480
980 1230 1480
S
mm
1700 1950 2200 1850 2100 2350 1850 2100 2350
H
mm
530
780 1030
530
780 1030
530
780 1030
F
mm
980
1240
1240
J
mm
410
450
450
K
mm
848
1048
1048
M
mm
270
300
300
N
mm
101
111
111
O
mm
767
937
937
P
mm
758
882
882
Q
mm
490
570
570
R
mm
900
1100
1100
V
mm
500
630
630
Heating coil
data
Coil type
A
B
C
A
B
C
A
B
C
Water content
l
3.1
3.1
6.2
4.7
4.7
9.4
4.7
4.7
9.4
L
"
Pipe thr. 1 ¼
(female)
Pipe thr. 1 ½
(female)
Pipe thr. 1 ½
(female)
Weight
Roof unit
kg
390
560
565
Below-roof unit (with F00)
kg
130
130
137
182
182
192
182
182
192
Filter box F00
kg
63
82
82
Heating section
kg
30
30
37
44
44
54
44
44
54
Air-Injector
kg
37
56
56
Total (with F00)
kg
520
520
527
742
742
752
747
747
757
Filter box F25
1)
kg
+ 11
+ 13
+ 13
Filter box F50
1)
kg
+ 22
+ 26
+ 26
1)
Additional weight compared to the design with filter box F00
Table B8: Dimensions and weights, RoofVent
®
LHW
RoofVent
®
LHW
Technical data
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......