3.5 Heat output
Temperature
of the fresh air
°C
0
-5
-10
-15
-20
of the extract air 18
14
13
12
11
10
20
16
15
14
13
12
22
18
17
16
15
14
24
19
18
17
16
15
26
21
20
19
18
17
Air inlet temperature at the heating coil
(with 20 % fresh air)
Table J6: Temperature change through intermixing of recirculation air (all values in °C)
t
AI
10 °C
15 °C
20 °C
LPHW
Size
Type
Q H
max
t
S
Δp
W
m
W
Q H
max
t
S
Δp
W
m
W
Q H
max
t
S
Δp
W
m
W
°C
kW
m
°C kPa
l/h kW
m
°C kPa
l/h kW
m
°C kPa
l/h
90/70
LK-6
C
86
8.4
59
9 3800
79
8.3
60
8 3500
72
8.3
60
7 3200
80/60
LK-6
C
73
9.1
52
7 3200
66
8.9
54
6 2900
59
8.8
55
5 2600
70/50
LK-6
C
59 10.2
44
5 2600
53
9.9
46
4 2300
46
9.7
47
3 2000
60/40
LK-6
C
45 12.0
36
3 2000
37 11.7
37
2 1600
29 11.7
37
2 1300
82/71
LK-6
C
82
8.6
57
24 6600
75
8.4
59
20 6000
68
8.3
60
17 5500
90/70
LK-9
C
131
9.0
59
8 5800 121
8.9
60
7 5300 110
8.9
60
6 4900
LK-9
D
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
80/60
LK-9
C
111
9.7
52
6 4900 101
9.5
54
5 4400
91
9.4
55
4 4000
LK-9
D
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
70/50
LK-9
C
91 10.9
44
4 4000
81 10.6
46
4 3500
71 10.3
48
3 3100
LK-9
D
124
9.2
57
9 5400 111
9.2
57
7 4800
98
9.1
58
6 4300
60/40
LK-9
C
69 12.8
36
3 3000
57 12.5
37
2 2500
44 12.5
37
1 1900
LK-9
D
99 10.4
47
6 4300
85 10.4
47
4 3700
69 10.4
47
3 3000
82/71
LK-9
C
125
9.2
57
21 10100 115
9.0
59
18 9200 105
8.9
60
15 8400
LK-9
D
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Legend:
t
AI
=
Air inlet temperature at the heating coil
Type =
Type of heating/cooling coil
Q
=
Heat output
H
max
=
Maximum mounting height (at room temperature 18 °C)
t
S
=
Supply air temperature
∆p
W
=
Water pressure drop
m
W
=
Water flow rate
— These operating conditions are not permissible, because the maximum supply air temperature of 60 °C is exceeded.
Table J7: Heat output, RoofVent
®
LK
RoofVent
®
LK
Technical data
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......