254
4 Design example
Note
The following design example relates to cooling mode. The design rating for heating mode can
be performed analogously to the design example above in Section I 'RoofVent
®
LH.'
Design data
■
Minimum fresh air flow rate or minimum air change rate
■
Minimum fresh air rate
■
Hall geometry (length, width, height)
■
Design conditions
■
Desired room temperature
■
Extract air temperature
■
Cooling load
■
Cooling medium
Note
If more than 40 % of fresh air is constantly required,
a unit with energy recovery is more economical.
1)
As a rule, the extract air temperature is higher than the temperature in the
occupied area. This is the result of unavoidable temperature stratification in
high spaces, but is reduced to a minimum with the Air-Injector. A tempera-
ture gradient of only 0.2 K per metre hall height can therefore be assumed.
Example
Minimum fresh air flow rate .......................17'500 m³/h
Minimum fresh air rate ......................................... 20 %
Hall geometry Space (L x W x H) ......... 108 x 40 x 9 m
Design conditions ...................................... 30 °C/40 %
Desired room temperature...................................24 °C
Extract air temperature ........................................26 °C
Cooling load..................................................... 260 kW
Cooling medium.................................... LPCW 6/12 °C
Room temperature:..............................................24 °C
Temperature gradient: .................................... 9 · 0.2 K
Extract air temperature: ....................................≈ 26 °C
Required number of units n
req
Based on the air flow rate per unit (see Table J4), select a
trial unit size. (Depending on the results of further calcula-
tions, repeat the layout design for another unit size if neces-
sary.)
n
req
= V
req
/ (V
U
· R)
V
req
= Required fresh air quantity in m³/h
V
U
= Air flow rate for the selected unit size in m³/h
R
= Minimum fresh air rate in %
Approximate selection: Unit size LK-9
n
req
= 17'500 / (7'650 · 0.2)
n
req
= 11.44
Select 12 LK-9s.
Actual fresh air flow rate V (in m³/h)
V
= n · V
U
· R
n
= Selected number of units
V = 12 · 7'650 · 0.2
V = 18'360 m³/h
Recirculation air flow rate V
R
(in m³/h)
V
R
= n · V
U
· (1 – R)
V = 12 · 7'650 · (1 – 0.2)
V = 73'440 m³/h
RoofVent
®
LK
Design example
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......