819682-UIM-A-0212

MODULAR
STANDARD ECM AIR HANDLERS

MODELS: MX

INSTALLATION MANUAL

ISO 9001

Certified Quality

Management System

LIST OF SECTIONS

GENERAL  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ELECTRIC HEATER INSTALLATION   . . . . . . . . . . . . . . . . . . . . . . . . 5
LOW VOLTAGE CONTROL CONNECTIONS   . . . . . . . . . . . . . . . . . . 6
REQUIRED CONTROL SET-UP  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

LINE POWER CONNECTIONS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8
BLOWER SPEED CONNECTIONS  . . . . . . . . . . . . . . . . . . . . . . . . . .  8
UNIT DATA   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  9
MAINTENANCE  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
WIRING DIAGRAM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15

LIST OF FIGURES

Typical Installation with MC or FC Evaporator Coil   . . . . . . . . . . . . . . . 3
Coil and Air Handler Attachment Details  . . . . . . . . . . . . . . . . . . . . . . . 3
Gasket Location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensions & Duct Connection Dimensions  . . . . . . . . . . . . . . . . . . . . 4
Duck Work Transition  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Horizontal Installation   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Control Board  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Line Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8
Blower Speed Connections   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8
Cooling Models with Electric Heat Wiring  . . . . . . . . . . . . . . . . . . . . .  13
Single-Stage Heat Pump Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13
Two-Stage Heat Pump Wiring   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
Wiring Diagram - MX12-16  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15
Wiring Diagram - MX20   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  16

LIST OF TABLES

Dimensions   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Low Voltage Connections   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Low Fan Control Inputs   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fault Codes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Blower Delays   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Heat Relays  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Physical and Electrical Data - Cooling Only (60 Hz)   . . . . . . . . . . . . . . 9
Electrical Data - Cooling Only (60 Hz)  . . . . . . . . . . . . . . . . . . . . . . . . . 9
Conversion Table  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Data - 1 Ø - 208/230-1-60   . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Electrical Data - (For Single Source Power Supply) - 
Copper Wire 1 Ø - 208/230-1-60   . . . . . . . . . . . . . . . . . . . . . . . . . . .  10
Electrical Data - (For Multi-Source Power Supply) - 
Copper Wire 1 Ø - 208/230-1-60   . . . . . . . . . . . . . . . . . . . . . . . . . . .  10
Electrical Data - 208/230-3-60   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11
Electrical Data - (For Single Source Power Supply) - 
Copper Wire - 208/230-3-60  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11
Electrical Data - (For Multi-Source Power Supply) - 
Copper Wire - 208/230-3-60  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11
Air Flow Data - 60 Hz Models  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12

SECTION I: GENERAL

This modular air handler provides the flexibility for installation in any
upflow, downflow, or horizontal application. These versatile models may
be used for cooling or heat pump operation with or without electric heat.

A BRAND LABEL (available from Distribution) may be applied to the
center of the blower access panel.

The unit can be positioned for bottom return air in the upflow position,
top return air in the downflow position, and right or left return in the hor-
izontal position.

Top and side power wiring and control wiring, accessible screw termi-
nals for control wiring and easy to install electric heaters all combine to
make the installation easy, and minimize installation cost.

SECTION II: SAFETY

This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.

Understand and pay particular attention to the signal words 

DANGER

,

WARNING

, or 

CAUTION

DANGER 

indicates an 

imminently

 hazardous situation, which, if not

avoided, 

will result in death or serious injury

.

WARNING 

indicates a 

potentially

 hazardous situation, which, if not

avoided, 

could result in death or serious injury

.

CAUTION 

indicates a potentially hazardous situation, which, if not

avoided 

may result in minor or moderate injury.

 It is also used to

alert against unsafe practices and hazards involving only property dam-
age.

Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Refer to this manual for assis-
tance or for additional information, consult a qualified contractor,
installer or service agency.

This product must be installed in strict compliance with the installation
instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical codes.

FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage.
A fire or electrical hazard may result causing property damage, per-
sonal injury or loss of life.

Summary of Contents for MX Series

Page 1: ...vailable from Distribution may be applied to the center of the blower access panel The unit can be positioned for bottom return air in the upflow position top return air in the downflow position and r...

Page 2: ...HUD modular home construction practices These instructions are required as a minimum for a safe installation INSPECTION As soon as a unit is received it should be inspected for possible dam age durin...

Page 3: ...document 13 Reposition and replace blower access panel AIR HANDLER AND COIL DOWNFLOW 1 Position blower casing over duct connection and secure such that the supply air end of the blower is down 2 Apply...

Page 4: ...insulation The supply air duct should be properly sized by use of a transition to match unit opening All ducts should be suspended using flexible hang ers and never fastened directly to the structure...

Page 5: ...heater is installed mark the name plate appropriately to indicate that no heat kit is installed The HEAT ENABLE jumper See Figure 10 must be moved to the HEAT position to enable operation of the heat...

Page 6: ...e HEAT position if a heat kit is installed with the air handler With the jumper in the NO HEAT position the control will not energize the heat relay outputs or sense the limit switch input If the jump...

Page 7: ...lay outputs and energize the blower if it wasn t already ener gized When the limit switch closes the control will re energize electric heat according to the thermostat inputs using normal timings Fan...

Page 8: ...ss current than copper conductors of the same size SECTION VIII BLOWER SPEED CONNECTIONS All air handlers contain a programmed 5 speed high efficiency brush less DC motor Adjust blower motor speed to...

Page 9: ...5 6 7 5 4HK 6501006 0 5 Med 3 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501306 0 5 Med 3 9 8 13 33 3 44 4 3 3 4 3 6 5 8 6 9 8 13 4HK165N1506 0 5 Med 3 10 8 14 4 36 9 49 1 3 6 4 8 7 2 9 6 10 8 14...

Page 10: ...0 110 3 3 4HK16502006 80 94 1 107 5 100 110 3 2 4HK16502506 100 115 7 132 5 125 150 1 1 0 1 O C P Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse TABLE 12 Electrica...

Page 11: ...4 18 24 1 See conversion Table 10 TABLE 14 Electrical Data For Single Source Power Supply Copper Wire 208 230 3 60 Models Heat Kit Three Phase Heater Amps 240V Field Wiring Min Circuit Ampacity Max O...

Page 12: ...0 70 0 80 0 90 1 00 0 025 0 050 0 075 0 100 0 125 0 150 0 175 0 200 0 225 0 250 MX12B Hi 1 1264 1241 1209 1184 1132 1067 1037 988 821 493 35 40 34 74 33 87 33 16 31 70 29 87 29 04 27 66 22 98 13 81 Me...

Page 13: ...move humidistat jumper on air handler control board 3 For heat pump applications set MODE jumper on air handler control board to the HP position 4 To change quantity of heat during HP defrost cycle re...

Page 14: ...1 and W2 on air handler control board SECTION X MAINTENANCE Filters must be cleaned or replaced when they become dirty Inspect at least once per month The frequency of cleaning depends upon the hours...

Page 15: ...819682 UIM A 0212 Johnson Controls Unitary Products 15 SECTION XI WIRING DIAGRAM FIGURE 13 Wiring Diagram MX12 16...

Page 16: ...otice Published in U S A 819682 UIM A 0212 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 628582 UIM A 0111 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 FIG...