background image

819682-UIM-A-0212

4

Johnson Controls Unitary Products

DUCT CONNECTORS

Air supply and return may be handled in one of several ways best
suited to the installation. See Figure 3 for dimensions for duct inlet and
outlet connections.

The vast majority of problems encountered with combination heating
and cooling systems can be linked to improperly designed or installed
duct systems. It is therefore highly important to the success of an instal-
lation that the duct system be properly designed and installed.

Use flexible duct collars to minimize the transmission of vibration/noise
into the conditioned space. If electric heat is used, non-flammable
material must be used.

Where return air duct is short, or where sound may be a problem,
sound absorbing glass fiber should be used inside the duct. Insulation
of duct work is a must where it runs through non-conditioned space
such as, attic or crawlspace. The use of a vapor barrier is recom-
mended to prevent absorption of moisture from the surrounding air into
the insulation.

The supply air duct should be properly sized by use of a transition to
match unit opening. All ducts should be suspended using flexible hang-
ers and never fastened directly to the structure. This unit is not
designed for non-ducted (freeblow) applications. Size outlet plenum or
transition to discharge opening sizes shown in Figure 3.

Duct work should be fabricated and installed in accordance with local
and/or national codes. This includes the standards of the National Fire
Protection Association for Installation of Air-Conditioning and Ventilat-
ing Systems, NFPA No. 90B.

 FIGURE 3:  

Gasket Location

 FIGURE 4:  

Dimensions & Duct Connection Dimensions

J

10-3/8”

E

CIRCUIT BREAKER

PANEL

BOTTOM INLET

DIMENSIONS

B

A

K

TOP OUTLET

DIMENSIONS

D

21-1/2”

20-1/2”

TABLE 1: 

Dimensions

Models

Dimensions

Wiring Knockouts

1

A

B

D

E

J

K

Height

Width

Power

Control

12B

25

17-1/2

16-1/2

14-19/32

7/8” (1/2”)
1 3/8” (1”)

1 23/32” (1 1/4”)

7/8” (1/2”)

12D

24-1/2

23-1/2

21-19/32

16C

21

20

18-3/32

20D

24-1/2

23-1/2

21-19/32

1. Actual size (Conduit size).

Use 1/2" screws to connect ductwork to bottom of unit. Longer screws
will pierce the drain pan and cause leakage. If pilot holes are drilled,
drill only though field duct and unit bottom flange.

Summary of Contents for MX Series

Page 1: ...vailable from Distribution may be applied to the center of the blower access panel The unit can be positioned for bottom return air in the upflow position top return air in the downflow position and r...

Page 2: ...HUD modular home construction practices These instructions are required as a minimum for a safe installation INSPECTION As soon as a unit is received it should be inspected for possible dam age durin...

Page 3: ...document 13 Reposition and replace blower access panel AIR HANDLER AND COIL DOWNFLOW 1 Position blower casing over duct connection and secure such that the supply air end of the blower is down 2 Apply...

Page 4: ...insulation The supply air duct should be properly sized by use of a transition to match unit opening All ducts should be suspended using flexible hang ers and never fastened directly to the structure...

Page 5: ...heater is installed mark the name plate appropriately to indicate that no heat kit is installed The HEAT ENABLE jumper See Figure 10 must be moved to the HEAT position to enable operation of the heat...

Page 6: ...e HEAT position if a heat kit is installed with the air handler With the jumper in the NO HEAT position the control will not energize the heat relay outputs or sense the limit switch input If the jump...

Page 7: ...lay outputs and energize the blower if it wasn t already ener gized When the limit switch closes the control will re energize electric heat according to the thermostat inputs using normal timings Fan...

Page 8: ...ss current than copper conductors of the same size SECTION VIII BLOWER SPEED CONNECTIONS All air handlers contain a programmed 5 speed high efficiency brush less DC motor Adjust blower motor speed to...

Page 9: ...5 6 7 5 4HK 6501006 0 5 Med 3 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501306 0 5 Med 3 9 8 13 33 3 44 4 3 3 4 3 6 5 8 6 9 8 13 4HK165N1506 0 5 Med 3 10 8 14 4 36 9 49 1 3 6 4 8 7 2 9 6 10 8 14...

Page 10: ...0 110 3 3 4HK16502006 80 94 1 107 5 100 110 3 2 4HK16502506 100 115 7 132 5 125 150 1 1 0 1 O C P Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse TABLE 12 Electrica...

Page 11: ...4 18 24 1 See conversion Table 10 TABLE 14 Electrical Data For Single Source Power Supply Copper Wire 208 230 3 60 Models Heat Kit Three Phase Heater Amps 240V Field Wiring Min Circuit Ampacity Max O...

Page 12: ...0 70 0 80 0 90 1 00 0 025 0 050 0 075 0 100 0 125 0 150 0 175 0 200 0 225 0 250 MX12B Hi 1 1264 1241 1209 1184 1132 1067 1037 988 821 493 35 40 34 74 33 87 33 16 31 70 29 87 29 04 27 66 22 98 13 81 Me...

Page 13: ...move humidistat jumper on air handler control board 3 For heat pump applications set MODE jumper on air handler control board to the HP position 4 To change quantity of heat during HP defrost cycle re...

Page 14: ...1 and W2 on air handler control board SECTION X MAINTENANCE Filters must be cleaned or replaced when they become dirty Inspect at least once per month The frequency of cleaning depends upon the hours...

Page 15: ...819682 UIM A 0212 Johnson Controls Unitary Products 15 SECTION XI WIRING DIAGRAM FIGURE 13 Wiring Diagram MX12 16...

Page 16: ...otice Published in U S A 819682 UIM A 0212 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 628582 UIM A 0111 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 FIG...

Reviews: