3.6 Heat output
Note
The performance data listed here applies to the most frequent design
conditions. Use the selection program 'HK-Select' to calculate the perfor-
mance data for other design data. You can download 'HK-Select' free of
charge on the Internet.
t
F
Q
Q
TG
H
max
t
S
°C
kW
kW
m
°C
-5
28
20
16.3
26
-15
22
11
21.7
23
Legend:
Q
=
Heat output
Q
TG
=
Output to cover fabric heat losses
H
max
=
Maximum mounting height
t
S
=
Supply air temperature
Room air 18 °C, extract air 20 °C/40 % rel. humidity
Table F7: Heat output, RoofVent
®
twin pump
Note
The output for coverage of the fabric heat losses (Q
TG
) allows for the
ventilation heat requirement (Q
V
) and the energy recovery output
(Q
ER
) under the respective air conditions. It is calculated as follows:
Q
TG
= Q + Q
ER
– Q
V
RoofVent
®
twin pump
Technical data