217
E
E
F
G
H
I
J
K
L
M
N
3.5 Heat output
Temperature
of the fresh air
°C
0
-5
-10
-15
-20
of the extract air 18
14
13
12
11
10
20
16
15
14
13
12
22
18
17
16
15
14
24
19
18
17
16
15
26
21
20
19
18
17
Air inlet temperature at the heating coil
(with 20 % fresh air)
Table I6: Temperature change through intermixing of recirculation air (all values in °C)
Unit size 6
t
AI
10 °C
15 °C
20 °C
LPHW
Size
Type
Q H
max
t
S
∆p
W
m
W
Q H
max
t
S
∆p
W
m
W
Q H
max
t
S
∆p
W
m
W
°C
kW
m
°C kPa
l/h kW
m
°C kPa
l/h kW
m
°C kPa
l/h
90/70
LH-6
A
44 14.1
33
9 1900
40 13.0
36
8 1800
37 11.9
40
7 1600
LH-6
B
57 11.9
40
15 2500
53 11.3
43
13 2300
48 10.7
46
11 2100
LH-6
C
92
9.2
58
10 4100
84
9.0
60
9 3700
77
9.0
60
8 3400
80/60
LH-6
A
37 16.2
29
7 1600
33 14.1
33
6 1500
30 13.0
36
5 1300
LH-6
B
48 13.3
35
11 2100
44 12.4
38
10 1900
39 11.7
41
8 1700
LH-6
C
78 10.0
51
8 3400
71
9.9
52
7 3100
63
9.6
54
5 2800
70/50
LH-6
A
30 18.8
26
5 1300
27 16.2
29
4 1200
23 14.1
33
3 1000
LH-6
B
39 15.0
31
8 1700
35 13.7
34
7 1500
30 13.0
36
5 1300
LH-6
C
64 11.3
43
6 2800
56 10.9
45
5 2500
49 10.6
47
4 2200
60/40
LH-6
A
22 25.0
22
3 1000
18 20.0
25
2
800
14 16.9
28
1
600
LH-6
B
30 18.8
26
5 1300
26 16.2
29
4 1100
20 15.0
31
3
900
LH-6
C
49 13.0
36
4 2100
40 12.7
37
3 1800
32 12.7
37
2 1400
82/71
LH-6
A
42 14.5
32
25 3400
39 13.0
36
22 3100
36 12.2
39
19 2900
LH-6
B
56 12.2
39
41 4500
51 11.5
42
35 4100
47 10.9
45
30 3700
LH-6
C
88
9.4
56
27 7000
80
9.2
58
23 6500
73
9.0
60
20 5900
Legend:
t
AI
=
Air inlet temperature at the heating coil
Type =
Type of heating coil
Q
=
Heat output
H
max
=
Maximum mounting height (at room temperature 18 °C)
t
S
=
Supply air temperature
∆p
W
=
Water pressure drop
m
W
=
Water flow rate
Table I7: Heat output, RoofVent
®
LH-6
RoofVent
®
LH
Technical data
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......