2.3 Operating modes
The RoofVent
®
LKW has the following operating modes:
■
Off
■
Ventilation
■
Ventilation (reduced)
■
Recirculation
■
Recirculation night
■
Exhaust air
■
Supply air
■
Night cooling summer
■
Emergency operation
The DigiNet control system controls these operating modes automatically per
control zone, in accordance with the scheduler (exception: emergency operation).
In addition, you can:
■
manually switch the operating mode of a control zone,
■
switch each individual RoofVent
®
unit to the following operating modes: Off,
Recirculation, Exhaust air, Supply air and Emergency operation.
Code
1)
Operating mode
Use
Diagram
Description
OFF
Off
The fans are turned off. Frost protec-
tion remains active. There is no room
temperature control.
If the unit is not
needed
Supply air fan ................... Off
Exhaust air fan ................. Off
Energy recovery ............... 0 %
Fresh air damper .............. Closed
Recirculation damper ....... Open
Heating/cooling ................ Off
VE2
Ventilation
The RoofVent
®
unit blows fresh air into
the room and draws off spent room air.
Heating/cooling and energy recovery are
controlled on the basis of heating/cooling
demand and temperature conditions.
The room temperature set value day is
active.
During room use
Supply air fan ................... On
Exhaust air fan ................. On
Energy recovery ............... 0 – 100 %
Fresh air damper .............. Open
Recirculation damper ....... Closed
Heating/cooling ................ 0 - 100 %
VE1
Ventilation (reduced)
Like VE2, but with reduced air flow rate
The room temperature set value day is
active.
During room use
(only for fans with
variable air flow
rate)
REC
Recirculation
On/Off operation: When heating or
cooling is required, the RoofVent
®
unit
draws in room air, heats or cools it and
blows it back into the room.
The room temperature set value day is
active.
For pre-heating and
pre-cooling
Supply air fan ................... On
*)
Exhaust air fan ................. Off
Energy recovery ............... 0 %
Fresh air damper .............. Closed
Recirculation damper ....... Open
Heating/cooling ................ On
*)
*) during heat or cool demand
RECN Recirculation night
Like REC, but with room temperature set
value night
During the night
and on weekends
RoofVent
®
LKW
Construction and operation
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......