44
3.3 Air flow rate, electrical connections
Unit type
LKW-6
LKW-9
LKW-10
Air distribution
Nominal air flow rate
1)
Supply air m³/h
5000
7650
8400
Exhaust air m³/h
5000
7650
8400
Floor area reached
Max.
m²
426
748
855
Energy recovery
Heat recovery efficiency, dry
%
60
63
57
Heat recovery efficiency, wet
%
68
73
65
Fan characteristics
Supply voltage
V AC
3 x 400
3 x 400
3 x 400
Permitted voltage tolerance
%
± 10
± 10
± 10
Frequency
Hz
50
50
50
Active power per motor
kW
1.8
3.0
4.5
Current consumption
A
4.0
6.5
9.9
Set point of thermal relays
A
4.6
7.5
11.4
Speed of rotation (nominal)
rpm
1440
1435
1450
Actuators
Supply voltage
V AC
24
24
24
Frequency
Hz
50
50
50
Control voltage
V DC
2…10
2…10
2…10
Torque
Nm
10
10
10
Run time for 90° rotation
s
150
150
150
Filter monitoring
Factory setting of differential pressure switch
Pa
300
300
300
1)
Refers to: RoofVent
®
LKW with heating/cooling coil type C and vertical supply air discharge direction
Table C4: Technical data, RoofVent
®
LKW
3.4 Sound levels
Unit type
LKW-6
LKW-9
LKW-10
Operating mode
VE2
REC
VE2
REC
VE2
REC
Position
Sound pressure level
(at a distance of 5 m)
1)
dB (A) 46 60 58 47 46 52 66 57 49 48 54 68 60 52 51
Total sound power level
dB (A) 68 82 80 69 68 74 88 79 71 70 76 90 82 74 73
Octave sound power level
63 Hz dB (A) 51 63 62 48 54 52 69 59 54 56 54 71 62 57 59
125 Hz dB (A) 55 71 70 56 63 63 78 70 60 63 65 80 73 63 66
2)
250 Hz dB (A) 61 76 74 64 63 65 81 71 63 66 67 83 74 66 69
500 Hz dB (A) 61 75 71 61 58 66 81 70 62 61 68 83 73 65 64
1000 Hz dB (A) 65 77 72 63 57 71 81 72 67 60 73 83 75 70 63
2000 Hz dB (A) 57 72 72 60 56 66 80 73 64 58 68 82 76 67 61
4000 Hz dB (A) 49 71 71 57 48 58 76 71 58 50 60 78 74 61 53
8000 Hz dB (A) 36 65 63 49 42 44 70 62 51 41 46 72 65 54 44
1)
with hemispherical radiation in a low-reflection environment
2)
outdoors (roof unit)
Table C5: Sound levels, RoofVent
®
LKW
RoofVent
®
LKW
Technical data
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......