3.5 Heat output
Note
The performance data listed here applies to the most frequent design conditions. Use the
selection program 'HK-Select' to calculate the performance data for other design data. You can
download 'HK-Select' free of charge on the Internet.
Fresh air tempera-
ture
-5 °C
-15 °C
Size
Q
Q
TG
H
max
t
S
Q
Q
TG
H
max
t
S
kW
kW
m
°C
kW
kW
m
°C
CON-9
60
40
14.1
33
60
32
15.7
30
Q
=
Heat output
Q
TG
=
Output to cover fabric heat losses
H
max
=
Maximum mounting height
t
S
=
Supply air temperature
Room air 18 °C, extract air 20 °C/40 % rel. humidity
Table G6: Heat output, RoofVent
®
condens in mixed air operation
Note
The output for coverage of the fabric heat losses (Q
TG
) allows for the ventilation heat requirement
(Q
V
) and the energy recovery output (Q
ER
) under the respective air conditions. It is calculated as
follows: Q
TG
= Q + Q
ER
– Q
V
RoofVent
®
condens
Technical data